Signal duplicator for process signals, isolated, for DIN rail mount.
Signal duplicator and signal converter, for process signals, isolated, for industrial applications. Accepts process signals in 4/20 mA and 0/10 Vdc, provides excitation voltage if needed. Dual output with 4/20 mA signals. Isolated 4 ways between power, input signal, output 1 and output 2. Universal power supply from 18 to 265 Vac/dc. Easy and fast configuration through configuration codes. Plug-in screw terminal connections. Functions to generate low and high output signals, to validate remote instrumentation. ‘Password’ function to block access to
configuration. Designed for industrial environment, for a wide range of applications, reduced cost, excellent quality, and optional customisation.
- Easy Configuration
- Information Display
- Fully configurable input and output ranges
- No configuration software needed, all done from the front panel
- Functions include Force and Password protection
| ITEM | DESCRIPTION |
|---|---|
| Input signal ranges Process | 4/20 mA, 0/10 Vdc (active and passive) excitation voltage +15 Vdc @30 mA |
| maximum over signal* | 25 mA, 25 Vdc |
| Accuracy at 25C | 0.3 % F.S. for mA, 0.3 % F.S. for Vdc |
| Thermal stability | 150 ppm/ºC (F.S.) |
| Output 1 signal ranges | active 4/20 mA signal 4/20 mA active, max. >20.5 mA, min. <1.0 mA, load < 400 Ohm passive 4/20 mA signal 4/20 mA passive, max. 30 Vdc on terminals |
| Output 2 signal ranges | active 4/20 mA signal 4/20 mA active, max. >20.5 mA, min. <1.0 mA, load < 400 Ohm passive 4/20 mA signal 4/20 mA passive, max. 30 Vdc on terminals |
| Configuration | keypad 2 keys display 2 digits, 7 segments, 5 mm height, red colour |
| Power | voltage range 20 to 240 Vdc ±10%, isolated 60 to 240 Vac ±10%, isolated AC frequency 45 to 65 Hz consumption <4.5 W power wires 1 mm2 to 2.5 mm2 (AWG17 to AWG14) overvoltage category 2 |
| Isolation 4 ways | between all circuits 2300 Veff (60 seconds) except input – output 2 1500 Vdc (60 seconds) |
| Housing | polyamide V0 |
| IP protection | IP30 |
| Mounting | Standard DIN rail (35 x 7.5 mm) |
| Size | 106 x 108 x 22.5 mm |
| Weight | <150 grams |
| Operating temperature | 0 to 50 degrees C |
| Storage temperature | -20 to 70 degrees C |
*’maximum over signal’ is the maximum signal accepted by the instrument. Higher signal values may
cause instrument damage. Lower values are non-destructive but may be out of accuracy specifications