Signal converter for impulses and frequency signals, isolated, for DIN rail mount..
Configurable to work with NPN, PNP, pick-up, Namur, mechanical contact, reed contact and other types of sensors. Dedicated input to measure frequency from AC signals up to 600 Vac. Accepts a wide range of frequency ranges, from 1 Hertz up to 1 MegaHertz. Output signal configurable for 4/20 mA (active and passive) and 0/10 Vdc. Universal power supply from 18 to 265 Vac/dc. 3 way isolation between input, output and power circuits. Predefined configuration codes for fast and easy configuration and advanced configuration to customize input and output signals ranges. Configuration through front push-button keypad and front display. Configurable information messages (input signal value, output signal value, configured label, signal percentage and process value). Manual ‘force’ functions to generate low and high output signals, to validate remote instrumentation during installation. ‘Password’ function to block non-authorized access to configuration menu. ‘SOS’ mode to help on critical maintenance and repairs without affecting the manufacturing process. Designed for industrial use, with potential integration into a wide range of applications, excellent quality and optional customization.
- Easy Configuration
- Information Display
- Fully configurable input and output ranges
- No configuration software needed, all done from the front panel
- Functions include Force, Label, SOS, On Error and Password protection
| ITEM | DESCRIPTION |
|---|---|
| Input signal types | NPN, PNP, pick-up, Namur, mechanical contact, reed contact and other types of sensors. Different signal types can be detected by configuring the sensor parameters at the configuration menu. Dedicated input to measure frequency from AC signals up to 600 Vac. |
| Input signal ranges Vdc | unipolar ranges from 0/50 mVdc up to 0/600 Vdc, bipolar ranges from +/-50 mVdc up to +/-600 Vdc |
| Input signal ranges Vac | Dedicated input to measure frequency from AC signals up to 600 Vac. |
| Frequency AC | Accepts a wide range of frequency ranges, from 1 Hertz up to 1 MegaHertz. |
| Output signal ranges | Active current output 4/20 mA active, max. <22 mA, min. 0 mA, load < 400 Ohm. Passive current output 4/20 mA passive, max. 30 Vdc on terminals. Voltage output 0/10 Vdc, max. <11 Vdc, min. -0.1 Vdc (typ.), load > 1 0Kohm. |
| Input Accuracy (%FS) | ‘slow’ mode error, f2 x 0.5 x 10-6 hz. ‘fast’ mode error, typical error is 2 Hz for a ‘gate’ of 0.5 seconds |
| Power | 18 to 265 Vac/dc isolated (20 to 240 Vac/dc +/-10%) |
| Consumption | <1.5 W |
| Power wire diameter | 1 mm2 to 2.5 mm2 |
| Housing | polyamide V0 |
| IP protection | IP30 |
| Mounting | Standard DIN rail (35 x 7.5 mm) |
| Size | 106 x 108 x 22.5 mm |
| Weight | <150 grams |
| Operating temperature | 0 to 50 degrees C |
| Storage temperature | -20 to 70 degrees C |
| Depth | 80 mm (including terminals) |